Kentucky · Journeyman & Master Plumber Licensing

Bluegrass Plumb Line

Your study bench for the Kentucky journeyman exam (target: November 2026) and the master exam after it. Built on KRS Chapter 318 and the Kentucky State Plumbing Code, 815 KAR Chapter 20. Progress saves in this browser.

Apply early. Your completed application must be in the Frankfort office at least 3 weeks before the exam date. For a November 2026 sitting, that means roughly mid-October — get the application in as soon as possible. Confirm the exact exam date and current fees with the Division of Plumbing: (502) 573-0397 · plumbing@ky.gov.

Journeyman Exam Your Nov 2026 target

Eligibility2 consecutive yrs as apprentice (or approved course + 1 yr)
Exam monthsFeb · May · Aug · Nov
FormatWritten 2½ hrs + practical 2½ hrs
Passing score75% on each portion
Exam fee$50 (non-refundable)
License fee$60 · renews on your birth month
Check-in7:30 a.m. · exam starts 8:00 a.m.

Master Exam Next step

EligibilityJourneyman license 2 of the last 5 yrs, working under a master
FormatWritten trade + law examination, drawing portion
Passing score80% (min 75% each portion)
Exam fee$150
License fee$250 · liability insurance required
Extra emphasisKRS 318 law, permits, business duties

What the exam covers

Per 815 KAR 20:030, both exams include written questions on the basic principles of plumbing, KRS Chapter 318 (the plumbing law), and 815 KAR Chapter 20 (the State Plumbing Code) — plus a drawing portion where you insert the proper pipe size on a prepared drawing showing all stacks, wastes, vents, and connected fixtures.

The regulation says main stacks are weighted more heavily than other piping on the drawing, and points are deducted for oversized as well as undersized pipe. "Bigger to be safe" loses points — practice exact sizing in the Pipe Sizing tab.

The journeyman practical also tests hands-on ability: making proper connections of various plumbing materials.

The road to master Master

  1. Nov 2026: pass the journeyman exam, get licensed.
  2. 2026–2028: keep the journeyman license active (renew each birth month, complete continuing education) while working under a master plumber.
  3. ~2028: after holding the journeyman license 2 years, apply for the master exam. It leans harder on KRS 318, permits (KRS 318.134), insurance (KRS 318.030), and running compliant jobs — everything in this site tagged Master is aimed there. The trade knowledge is the same code, tested deeper.

Official resources

Division of Plumbing · 500 Mero Street, Frankfort, KY 40601 · (502) 573-0397 · plumbing@ky.gov

Plain-English walkthroughs of what the exam draws from. Each section names its source so you can pair it with the official code book — order the current book from the Division page first; this guide is the map, the book is the territory.

Study smarter — the playbook

How to study

  • Study the RIGHT code. Nationally, the #1 reason candidates fail is studying IPC or UPC when their state uses something else — and Kentucky has its own plumbing code with its own fixture units and tables. Everything on this site is keyed to the KY code. Ignore generic national prep.
  • Practice testing beats rereading. Testing yourself is the most effective study technique known — successful candidates work through hundreds of questions. Quizzes and sims here count toward that; retaking a quiz you aced last week still strengthens recall.
  • Short daily sessions beat weekend binges. 20–30 minutes a day (spaced repetition) outperforms a 4-hour Saturday cram. The flashcard "got it" system and the smoke quizzes are built for lunch breaks.
  • Keep an error log. It's automatic here: every question you miss lands in the "My missed questions" deck in the Quiz tab. Answer one correctly and it retires. Drill it to zero before exam week.
  • Recall before you look. Before opening a table, say the answer out loud, then check. And teach what you learned — explaining trap-arm limits to an apprentice on the job is the strongest encoding there is.
  • Anchor to the jobsite. Each study week, find that week's rules in your actual work: trace the cleanouts, measure a trap arm, check the water heater pan.

Test day

  • Three passes. Pass 1: answer everything you know cold. Pass 2: work the ones you skipped. Pass 3: review flags. Never leave a blank — a guess beats a blank every time.
  • Read the last sentence of the question first — it tells you what's actually being asked; then read the setup for the numbers.
  • Eliminate before you choose. Cross out the two clearly wrong options; be suspicious of "always" and "never"; code answers are usually the precise number, not the round one.
  • Don't change answers without a concrete reason — first instincts on code questions are right more often than not.
  • Pace: at the 75-minute mark of each 2½-hour portion you should be at least halfway. If a question eats 3 minutes, flag it and move.
  • Drawing portion: size the main stack first (it's weighted most), work downstream to upstream, and remember: exact size — oversizing loses the same points as undersizing.
  • Logistics: in bed early, check-in 7:30 a.m. in Frankfort, ID and confirmation in hand.

The practical portion — hands-on 2½ hours · many fail here

What you'll build

  • A caulked lead joint on cast iron: pack the oakum tight and even, pour the molten lead in one continuous pour, then caulk (set) the cooled lead inward and outward. Dry joint, dry ladle — moisture makes lead spatter violently.
  • A copper offset project using 45° elbows — measured, cut, reamed, cleaned, fluxed, and soldered to dimensions given on a drawing.
  • Candidates report the #1 reason for failing is cutting pipe lengths wrong — not bad soldering. The offset math below is the whole game.

Offset math — memorize this

  • For a 45° offset: travel (the diagonal piece) = offset × 1.414. A 12″ offset needs a travel of ~17″ center-to-center.
  • Other multipliers: 60° → 1.155 · 30° → 2.000 · 22½° → 2.613. (Offset = the perpendicular distance between the two pipe centerlines.)
  • Then subtract fitting takeoff: measure center-to-center, deduct each fitting's allowance (center of fitting to face of socket) to get the actual cut length — measure twice, cut once, dry-fit before soldering.
  • Practice at the shop: build the same 45° offset three times against a tape until your cuts land within 1/16″.

The law: KRS Chapter 318 JM

  • 318.010 — Definitions. Know "plumbing," "master plumber," "journeyman plumber," "apprentice."
  • 318.020 — Exemptions: apprentices working under supervision, maintenance men, water company/district employees.
  • 318.030License required to engage in the plumbing trade; masters must also carry general liability insurance.
  • 318.040 — Qualifications, examinations, reciprocity.
  • 318.050 / .054 — Fees; licenses expire on your birth month; renewal requires continuing education.
  • 318.060 — Reexamination after a failure.
  • 318.064 / .066 — License revocation/suspension; hearings and appeals.
  • 318.080 — State Plumbers Examining Committee.
  • 318.090 / .140 — Plumbing inspectors; local governments enforce the State Plumbing Code.
  • 318.120Employing an unlicensed plumber is prohibited.
  • 318.130 — The Department of Housing, Buildings and Construction adopts the State Plumbing Code by regulation.
  • 318.134Installation permits: required before plumbing is installed; know who obtains them and when. Master-exam favorite.
  • 318.160 — Installation plans and specifications.
  • 318.200 — Water heating devices and serial numbers.

Licenses & exams: 815 KAR 20:030

The licensing regulation — the exam facts on the first tab come from here. Memorize: journeyman needs 2 consecutive apprentice years (or approved course + 1 year); master needs a journeyman license 2 of the preceding 5 years; journeyman passes at 75%, master at 80%; exams run quarterly; applications due 3 weeks ahead.

Permits & fees: 815 KAR 20:050 & KRS 318.134 Master favorite

  • Permit required for: new installations, relocated fixtures, replaced house sewers or water services, backflow preventers, and new or replaced water heaters.
  • No permit needed for: repairing leaks, cocks, and valves, or cleaning waste pipes.
  • Who can pull one: a licensed master plumber — or a homeowner who applies before starting, files a compliance affidavit, does the work personally, and hasn't held a homeowner permit in the past 5 years.
  • Fees (since 3/1/2022): residential $50 base + $14 per fixture/opening; commercial $50 base + $20 per fixture/opening/conductor; water-heater-only permit $50 flat.
  • Five inspections included; additional inspections $50 each (waived if the permit cost over $250).
  • Permits expire after one year unless construction is ongoing; void if work stops 12+ months.

Definitions: 815 KAR 20:010

  • Developed length — length measured along the center line of pipe and fittings. Trap-arm and vent limits are developed length.
  • Fixture unit — the code's load measure for drainage and supply; roughly 7½ gal/min (1 cu ft/min) of discharge.
  • Soil pipe vs. waste pipe — soil pipe carries discharge from water closets/urinals (fecal matter); waste pipe carries other fixture discharge.
  • Stack — the vertical main of a soil, waste, or vent system. Stack vent = the extension of a soil/waste stack above the highest horizontal drain. Vent stack = a vertical pipe installed purely to provide air circulation.
  • Building (house) drain — lowest horizontal piping inside the building; it becomes the building sewer 2 feet outside the building wall. That 2-foot line is a favorite test question.
  • Trap arm — the portion of the fixture drain between the trap and its vent.
  • Branch interval — a story height along a stack, but never less than 8 feet.
  • Horizontal vs. vertical pipe — horizontal is less than 45° from horizontal; vertical is 45° or less from vertical.
  • Hot water — water at not less than 120°F.
  • The vent family — individual, branch, common (junction of two fixture drains), continuous, circuit (2+ traps to a vent stack), loop (same but back to the stack vent), relief (extra air circulation), and yoke (stack-to-vent-stack, relieves pressure in tall stacks). The exam loves telling these apart.
  • Air break — indirect discharge below the flood level rim (the air gap is above it).
  • Critical level — how deep a vacuum breaker can be submerged before backflow; if unmarked, the bottom of the device.
  • Trap seal — the water in a trap between dip and crown weir that blocks sewer gas.
  • Air gap — unobstructed vertical distance between a supply outlet and the flood-level rim.
  • Cross-connection / backflow — any link between potable and non-potable water; the code exists to prevent it.
  • Wet vent — a vent that also serves as a drain for other fixtures.

Fixtures: 815 KAR 20:070 & 20:191

  • Overflows are optional — but if used, they connect to the inlet side of the trap and stay accessible for cleaning.
  • Traps and pipes stay at least 12″ off the floor (laundry trays excepted); pipes run to the wall.
  • Water closets: one-piece bowls with integral flushing rims; max 1.6 gal/flush residential, 3.5 gal/flush commercial.
  • Showers: pans turn up the walls at least 6″; heads flow at most 2.5 gpm.
  • Floor/shower drains are fixtures; strainer outlet area ≥ the trap's interior area.
  • 20:191minimum fixture counts: every dwelling unit gets at least one water closet, one lavatory, and one bathtub or shower. Employee facilities are separate by sex when more than 5 employees work in the building. Dormitories: 1 WC per 10 persons. Schools: at least 2 water-bottle filling stations plus one fountain per 75 students; fountain orifices sit 1″ above the overflow rim with a protective cowl.

Special connections: 815 KAR 20:180

  • A/C condensate (evaporative coolers, air handlers) is never directly connected to soil, waste, or vent piping — indirect waste through an air gap into a floor drain or approved receptor.
  • Commercial laundries: at least a 4″ trap with full-size vent; semicommercial machines share a 4″ waste/trap with max 2 machines, counted as 4 FU.
  • Flammable waste (gasoline, benzine, naphtha) discharges through a separator before the sanitary sewer, vented with a 3″ vent.
  • Garage sand traps: concrete, minimum 2′ × 4′, 10″ from outlet to trap bottom, 4″ vent.
  • Pedicure chairs: up to 2 chairs → 2″ receptacle; 3–6 chairs → 3″ minimum; high-hazard setups need RPZ backflow preventers on hot and cold supplies.

Medical gas piping: 815 KAR 20:195 Master

  • Installers must be BOTH a certified medical gas installer per NFPA 99 AND a licensed master or journeyman plumber.
  • Installations follow NFPA 99 (Health Care Facilities Code) — incorporated by reference.
  • The supervising master plumber verifies installer qualifications, proper products and storage, requests inspection at the initial pressure test, and submits the system verifier's certification to the division at completion.
  • Permit: $50 per building + $20 per opening.

Manufactured & mobile home communities: 815 KAR 20:170

  • Every home gets a 4″ sewer; the home's waste connection to it is at least 3″.
  • Branch sewers by community size: 1–10 homes → 4″ · 11–20 → 5″ · 21–50 → 6″ · 51–150 → 8″ · 151–300 → 10″.
  • Water services by count: 1–2 homes → ¾″ · 3–6 → 1″ · 7–12 → 1¼″ · 13–20 → 1½″ · 21–50 → 2″ · 51–100 → 3″.
  • Water risers terminate ≥ 4″ above ground with a ¾″ valve, encased in 8″ vitrified clay pipe (or equal) packed with insulation against freezing.
  • Piping with less than 18″ of cover must be cast iron.

Materials & supports: 815 KAR 20:060

  • Lead pipe is prohibited in potable water systems. Approved: copper, CPVC, PEX, galvanized steel (water); cast iron, PVC/ABS Schedule 40/80, copper (drainage).
  • PVC/ABS height limit: buildings not exceeding 45 feet (applies to DWV and storm conductors).
  • Horizontal support spacing: copper ≤1″ → 6′, ≥1¼″ → 10′ · steel ≥1½″ → 12′, ≤1¼″ → 8′ · PVC/ABS → 4′ · CPVC ≤1″ → 3′ · PEX ≤1″ → 32″, ≥1¼″ → 48″.
  • Vertical: copper 1½″+ at each story; screwed steel every other story.
  • Joints: unions ground-faced and never concealed; no fittings with enlargement chambers or ledge shoulders in drainage.
  • Storage: PEX away from UV and petroleum; solvent cement away from ignition and never past shelf life; plastic pipe lifts stacked max 3 high.

Waste pipe sizes: 815 KAR 20:080 Heavily tested

Minimum trap and branch sizes per fixture — these are pure memorization and show up in both the written and drawing portions. The core table is in the Pipe Sizing tab. Anchors: lavatory 1¼″ · tub, shower, kitchen sink 1½″ · clothes washer 2″ · water closet 3″ · floor drain 3″ (industrial 4″).

Soil, waste & vent systems, traps, cleanouts: 815 KAR 20:090 The big one

  • Traps: every fixture individually trapped, as near the fixture as possible — max 10″ vertical from fixture outlet to the trap's seal dip. Water seal at least 2″, no more than 4″.
  • Trap-to-vent distance: every trap needs a vent within a maximum developed length that depends on drain size (e.g., 1½″ drain → 3′6″; 4″ drain → 10′). Full table in Pipe Sizing.
  • Vent sizing: tables give maximum fixture units and maximum developed length per vent diameter (e.g., 1¼″ vent → 2 FU; 3″ vent → 72 FU at up to 300′).
  • Stacks: soil and waste stacks extend full size through the roof, minimum 3″ where they pass through, terminating at least 1′ above the roof5′ where the roof is a deck/promenade; 2′ above any window or door within 10′ (unless screened); increasers go at least 1′ below the roof.
  • The water closet rule: max 3 standard WCs per 3″ soil pipe (4 if all are 1.6 gpf); WC fixture branch no longer than 4′6″.
  • Grade: horizontal drainage runs at a uniform grade of at least 1/8″ per foot.
  • Cleanouts: max 150′ apart in sewers; at the base of each stack where stacks exceed 45′; same nominal size as the pipe they serve (within limits); accessible.
  • Prohibited traps (basic principles): S-traps, bell traps, crown-vented traps, traps depending on moving parts.

Water supply: 815 KAR 20:120

  • Water service: minimum ¾″ from the main to the building, sized for continuous, ample flow.
  • Distribution: hot and cold mains minimum ¾″ to the first branch; no more than three ½″ fixture branches on one ½″ line; concealed branches minimum ½″.
  • Backflow protection: the air gap is the best protection in all situations. Minimum gaps run from 1″ (lavatories) to 3″ (bath fillers near walls). RPZ (reduced pressure zone) assemblies must be tested at least annually.
  • Cross-connections: private water supplies may never be interconnected with a public supply.
  • Thermal expansion: where a check valve closes the system, install a thermal expansion tank (or other relief) on the cold supply near the water heater.

Water heaters: 815 KAR 20:055 & KRS 318.200

  • T&P relief valve on the hot side, within 3″ of the top of the heater — full-size drain, never trapped or valved off.
  • Discharge: with a floor drain, pipe to within 2″ of the floor; without one, pipe outside with an ell turned down, within 4″ of the ground.
  • Tankless (instantaneous): relief valve rated no more than 150 psi.
  • Space heating combo: water temperature max 140°F; above 210°F the unit falls under KRS 236 pressure-vessel rules.
  • Pans: attic, drop-ceiling, or wood-floor installations (post-4/1/2021) need a corrosion-resistant watertight pan with at least a ¾″ drain.
  • Heaters stay accessible for inspection, repair, and replacement. KRS 318.200 covers serial numbers.

House sewers & storm water: 815 KAR 20:130

  • Minimum house sewer: 4″, and never smaller than the house drain it serves.
  • Grade: between 1/8″ and 1/4″ per foot — too steep is a violation too (solids get stranded). A classic exam trap.
  • Cover: 18″ minimum; 24″ under driveways/parking unless approved pipe encased in concrete.
  • Materials: cast iron, vitrified clay, concrete, PVC/ABS, truss, PE (per ASTM). Inside storm conductors: cast iron, galvanized steel, copper, or approved plastic — plastic limited to buildings ≤ 45′.
  • Storm sizing: roof area at a 4″-per-hour rainfall baseline.
  • Trench stays open for inspection; backfill hand-tamped to 6″ above the pipe.

Inspections & tests: 815 KAR 20:150 Know cold

  • Rough-in inspection before anything is concealed; final inspection at completion. The permit holder requests both.
  • Alterations/repairs involving more than 10′ of soil, waste, or vent piping require inspection.
  • Water test: by sections with at least a 10′ head; whole system filled to overflow. Water distribution tests at max working pressure.
  • Rough air test: 5 psi held 15 minutes.
  • Final air test: 1″ water column, 15 minutes, on the entire soil-waste-vent system including fixtures — everything except the house sewer.
Question
Loading…
Answer
Click card or press Space to flip · / to move

"Got it" hides a card from the rotation (per deck) so you drill what you don't know. Reset anytime.

Exam-style multiple choice with explanations. The real journeyman written passes at 75%, master at 80% — the score screen shows both lines.

Browse the bank

Search every question as a study reference — correct answers and explanations shown.

Full written-exam simulation: timed 2½ hours, no feedback until you submit — just like exam day in Frankfort. Answer in any order, flag questions to revisit, and get a category breakdown at the end. (The real exam also has a drawing/practical portion — drill that in the Pipe Sizing tab.)

Journeyman simulation Pass: 75%

60 questions across every trade topic — law, definitions, DWV, water, sizing, fixtures, materials, tests.

Master simulation Pass: 80%

60 questions including every master-level law and administration question, plus the full trade bank.

The drawing portion gives you a layout of stacks, wastes, vents, and fixtures — you write in the pipe sizes. Main stacks are weighted most, and oversizing loses points just like undersizing. This tab covers the method, the tables, and drills.

The method — five steps

  1. Identify every fixture on the drawing and assign its fixture-unit (FU) load from the table.
  2. Size each fixture branch and trap from the minimum-size table — these are fixed minimums, no math.
  3. Work downstream: total the fixture units at each horizontal branch and each stack section, and size from the FU-capacity table. A pipe never gets smaller in the direction of flow.
  4. Check the special rules: any stack serving a water closet is at least 3″; stacks run full size through the roof (3″ minimum at the roof, 1′ above it); no drain smaller than its trap.
  5. Size the vents: every trap vented within its distance limit; vent size from the vent table (diameter vs. FU served vs. developed length).

Trap, branch & fixture-unit values — 815 KAR 20:080

FixtureMin trapMin branchFixture units
Lavatory1¼″1¼″1
Drinking fountain1¼″1¼″1
Bathtub1½″1½″
Shower stall1½″1½″
Kitchen sink1½″1½″
Bar / soda fountain sink1½″1½″
Urinal — lip1½″1½″
Clothes washer (standpipe)2″2″2
Urinal — stall2″2″2
Floor drain — residential laundry2″2″2
Floor drain — toilet / utility room3″3″3
Urinal — pedestal3″3″3
Water closet — over 1.6 gpf3″ (integral)3″–4″6
Water closet — 1.6 gpf or less3″ (integral)3″–4″4
Floor drain (industrial)4″4″4
The Kentucky shortcut: in this table the fixture-unit value almost always equals the trap size in inches (1½″ trap → 1½ FU, 2″ → 2, 3″ → 3). The exceptions to memorize are the water closets: 6 FU standard, 4 FU at 1.6 gpf or less. A full bath group = WC 6 + lav 1 + tub 1½ = 8½ FU (6½ with a low-flow WC).

Trap-to-vent distance — 815 KAR 20:090 §2

Drain sizeMax developed length, trap to vent
1¼″2′ 6″
1½″3′ 6″
2″5′
3″6′
4″10′

Soil & waste stack capacity — 815 KAR 20:090 §10

Stack sizeMax fixture unitsMax developed length
1¼″125′
1½″260′
2″680′
2½″12100′
3″36225′
4″172unlimited
5″342unlimited
6″576unlimited
The water closet rule: a WC needs at least a 3″ soil pipe, and no more than three water closets (or soil-discharging fixtures) may discharge into one 3″ pipe — four allowed if every one flushes at 1.6 gpf or less. A WC's fixture branch may be no longer than 4′ 6″.

Vent capacity — 815 KAR 20:090 §20

Vent sizeMax fixture unitsMax developed length
1¼″230′
1½″10150′
2″24200′
2½″36250′
3″72300′
4″240400′
5″420600′
6″720800′

Key vent & stack rules

  • Soil/waste stacks: full size through the roof, 3″ minimum at the roof, terminate ≥ 1′ above it — but ≥ 5′ where the roof is used as a deck or promenade.
  • A vent terminal within 10′ of a window or door must extend 2′ above the opening's top edge (unless screened).
  • A stack smaller than 3″ increases to 3″ with the increaser fitting at least 1′ below the roof.
  • Horizontal drainage piping: uniform grade, minimum 1/8″ per foot.
  • Trap seal 2″–4″; fixture outlet to trap dip ≤ 10″; branch interval never less than 8′.
  • Cleanouts ≤ 150′ apart on sewers; at stack bases over 45′.
Everything on this tab is now the official code text: per-fixture values from 815 KAR 20:080, and the stack, vent, and trap-arm tables from 20:090. These are the exact tables the drawing portion is graded against.

Drills

Offset trainer — infinite practical math Streak game

The practical exam's make-or-break skill, generated fresh every time: offsets, travels, and cut lengths. Build a streak — a wrong answer resets it.

Streak: 0

Drawing practice — size the riser

This is the drawing portion in miniature. Each lettered segment on the diagram needs a size — pick from the dropdowns, then grade. Scoring mirrors the real exam: the main stack and stack vent count double, and an oversized pipe scores zero just like an undersized one. 75% passes journeyman, 80% master.

The written exam is closed book — the code numbers have to live in your head. Number Race drills instant recall: a rule flashes up, you name the number — 15 seconds each, 10 rounds. Faster answers score more; a miss shows the right value.

Keys 1–4 answer. Scoring: 10 points + 1 per second left. Perfect-run ceiling ≈ 250.

Or press Ctrl+P with this tab open — only the cheat sheet prints. Every number below is from the cited regulation.

Exam day — 815 KAR 20:030

  • Quarterly: Feb · May · Aug · Nov, Frankfort
  • Application in office 3 weeks prior
  • Check-in 7:30 a.m., start 8:00
  • Written 2½ h + practical 2½ h
  • Journeyman: 75% each portion · $50 exam / $60 license
  • Master: 80% (75% floor) · $150 / $250 + liability ins.
  • J: 2 consecutive yrs apprentice · M: journeyman 2 of last 5 yrs
  • License expires on birth month; CE to renew

Fixture units — 20:080

Lavatory · drinking fountain1¼″ · 1 FU
Tub · shower · kitchen sink · bar sink · lip urinal1½″ · 1½ FU
Clothes washer · stall urinal · laundry FD2″ · 2 FU
Toilet/utility FD · pedestal urinal3″ · 3 FU
WC standard / ≤1.6 gpf3″ · 6 / 4 FU
Industrial floor drain4″ · 4 FU
  • FU = trap size in inches (except WCs)
  • Bath group: 8½ FU (6½ low-flow)
  • 1 FU ≈ 1 cfm ≈ 7½ gpm

Stack capacity — 20:090 §10

SizeFULen
1¼″125′
1½″260′
2″680′
2½″12100′
3″36225′
4″172
5″ / 6″342 / 576
  • Max 3 soil fixtures per 3″ (4 WCs if all 1.6 gpf)
  • WC branch ≤ 4′6″

Vent capacity — 20:090 §20

SizeFULen
1¼″230′
1½″10150′
2″24200′
2½″36250′
3″72300′
4″240400′
5″ / 6″420 / 720600′ / 800′

Trap → vent distance — 20:090 §2

1¼″2′ 6″seal 2″–4″
outlet→dip ≤10″
1½″3′ 6″
2″5′
3″6′
4″10′
  • No S-traps, bell traps, crown vents

Stacks, roofs & cleanouts — 20:090

  • Full size through roof, 3″ min, ≥ 1′ above
  • Roof deck/promenade: ≥ 5′
  • Within 10′ of window/door: 2′ above top (or screen)
  • Increaser ≥ 1′ below roof
  • Horizontal grade ≥ 1/8″/ft
  • Branch interval ≥ 8′
  • Cleanouts: sewers ≤ 150′ apart; base of stacks > 45′

Water supply — 20:120

  • Service ≥ ¾″; concealed branches ≥ ½″
  • Max three ½″ branches per ½″ line
  • Air gap = best protection (1″–3″ by fixture)
  • RPZ tested annually
  • No private ↔ public interconnection
  • Check valve → expansion tank at heater
  • Hot water = 120°F min
  • Building drain → sewer at 2′ outside wall

Water heaters — 20:055

  • T&P valve ≤ 3″ from top, hot side
  • Discharge: ≤ 2″ of floor; no drain → outside, ell down, ≤ 4″ of ground
  • Tankless relief ≤ 150 psi
  • Space heating ≤ 140°F; > 210°F → KRS 236
  • Attic/wood floor: watertight pan, ¾″ drain

Tests & inspections — 20:150

  • Rough-in before concealment; permit holder requests
  • Alterations > 10′ of pipe → inspection
  • Water: 10′ head by section; whole system to overflow
  • Rough air: 5 psi · 15 min
  • Final air: 1″ water column · 15 min — all DWV + fixtures, except house sewer
  • Water piping: max working pressure

Sewers & storm — 20:130

  • House sewer ≥ 4″, never < house drain
  • Grade 1/8″–1/4″ per ft (steeper fails too)
  • Cover 18″; traffic areas 24″
  • Trench open for inspection; hand-tamp 6″ over pipe
  • Storm design: 4″/hr rainfall
  • Plastic (PVC/ABS) only in buildings ≤ 45′

Fixtures & materials — 20:070 / :060

  • WC ≤ 1.6 gpf res / 3.5 comm; shower pan 6″ up; head ≤ 2.5 gpm
  • Overflow → trap inlet side; pipes ≥ 12″ off floor
  • No lead in potable; unions ground-faced, exposed
  • Supports: Cu 6′/10′ · steel 12′/8′ · PVC 4′ · CPVC 3′ · PEX 32″/48″
  • PEX: no UV · cement: shelf life, no flame

Permits — 20:050 / KRS 318.134

  • Res: $50 + $14/fixture · Comm: $50 + $20
  • Water-heater permit $50 (replacement needs one!)
  • Exempt: repairing leaks, cocks, valves; cleaning waste pipes
  • Master or homeowner (affidavit, self-work, 5-yr rule)
  • Expires 1 year; 5 inspections incl., extras $50
  • Special: A/C = indirect · laundry 4″ trap · sand trap 2′×4′ · separator w/ 3″ vent

Practical portion & offsets

Fitting angleTravel = offset ×
45°1.414
60°1.155
30°2.000
22½°2.613
  • Cut length = center-to-center − fitting takeoffs
  • Lead joint: pack oakum → one continuous pour → caulk in & out · everything DRY
  • Copper: cut · ream · clean · flux · heat the fitting · feed solder · wipe
  • #1 practical failure: wrong cut lengths — dry-fit first

Twelve weeks from late August to the November exam. Each week has a reading focus and drills; checkboxes save in this browser.

After November: when you pass, come back — the Master-tagged decks and quizzes, plus the KRS 318 guide, are the core of master-exam prep. You'll add depth on permits, insurance, and running jobs while you log your two years as a journeyman.

Backup & restore progress

Your streaks, scores, and checklists live in this browser. To move them to another device: Show backup code here, copy it, then paste it on the other device and hit Restore.

Sources & accuracy. Compiled August 2026 from KRS Chapter 318, 815 KAR Chapter 20 (20:010, :030, :050, :055, :060, :070, :080, :090, :120, :130, :150, :180, :191), and the KY Division of Plumbing. This is a study aid, not the code — always verify against the current official Kentucky Plumbing Law, Regulations and Code Book and confirm exam dates, deadlines, and fees with the Division of Plumbing at (502) 573-0397.